LW3F series 15KV27KV38KV SF6 Load Break Switch

Model Series
LBS
Rated Voltage
2.5~34.5kV
Standard
IEC 62271-1
Warranty
Two years
Application
Outdoor/Indoor
Contact Us
Download

LW3F type pole-mounted SF6 load break switch was used in 12kV,24kV,33kV rated voltage, rated current 400/630A; 50/60HZ with the load current; over load current of power line open circuit and opening and closing electric systems.

General

The switch can equipped with a controller with most advanced technical parameter.
LW3F-A type LW3F is manually LBS for choice.
LW3F-M type LW3F is a intelligent type LBS for choice.
It can automatically disconnect when the distribution line was break down.
It could operated by handle; Implement electrification and distant. The electric controller was installed in stainless steel cabinet. So it could use in any conditions.

Service Condition

  1. Air temperature: Maximum temperature: +40 ; Minimum temperature:-20.
  2. Humidity: Monthly average humidity 95%; Daily average humidity 90%.
  3. Altitude above sea level: Maximum installation altitude: 2500m.
  4. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
  5. No frequent violent shake.

Product Structure

Product Characters:
●High quality porcelain or Rubber bushing
●Full comply with IEC std
●Guarantee 4000 times operations
●Environment friendly
●Suitable for both Pole mounted or Hanging mounted
●Reliable and Enhanced Life Expectancy
●Ambient Temp:-40℃~+ 80℃
Operation Handle ON/OFF Indication Installation Bracket
Operating Mechanism Interrupter Hanging Lug
Cable Bushing      

Controller

1.1 Description

Volt logic series line sectional load break controller is medium voltage overhead line grid monitoring unit, It can combined with load break switch for achieve of measure monitoring, fault analysis and event records. It gives us a safety power grid for cutting line fault and automatic recovery operation and power automation.

The controller is gathering with line protection, control, measurement and monitoring of voltage and current signals integrated automation and control devices outdoors.

The controller is a automatic management unit for single way/multi ways/ring network /two power sourcing, provided with all voltage and current signals and all functions.

The controller column switch intelligent controller supports:Wireless (GSM/GPRS/CDMA), Ethernet mode, WIFI, optical fiber, power line carrier, RS232/485, RJ45 and other forms of communication, and can access other station premises equipment (such as TTU, FTU, DTU, etc.).

1.2 Protection functions

Protection functions ANSI code Name in Device
Phase overcurrent 50P P.OC
Overload 49 Overload
Phase Time-Overcurrent 51P P.Curve
Ground Overcurrent 50G/N E.F
Recloser 79 Reclose
Phase overcurrent cold load pick-up CLPU50 Cold Load
Switch-Onto-Fault   SOTF
Undervoltage 27 Under volt
Overvoltage 50P P.OC
1.3 Metering
●Phase current IA, IB, IC RMS, Zero Sequency
●Voltage Uab, Ubc, Uca, U0
●Active power, reactive power and power factor
●Frequency
 
1.4 Control and monitoring
Switch control 94
Lockout Relay 86
1.5 Features
●Protection configuration is complete, and all protection functions can be switched on and off flexibly.
●13 channels digital signal input.
●4 channels current measure.
●6 channels voltage measure.
●Large capacity flash memory can record at least 100 times of historical events and no data will loss even the power is off.
 
1.6 Records
●Trip logs
●SOE logs
●Alarm Logs
 
1.7 Communication
●RS485, RS232 port and Ethernet
●Protocols -IEC60870-5-101, IEC60870-5-104
IEC61850 or Modbus RTU,DNP3.0
 
1.8 HMI Software

Dimensions

15KV SF6 LOAD BREAK SWITCH
36KV SF6 LOAD BREAK SWITCH

Installation

Technical Data

No Item Unit Data
1 Rated voltage kV 12-20-33
2 Rated current Hz 50/60
3 Rated insulation level (with SF6 gas 0.07Mpa) lightning impulse voltage kV 75/125/170
Power frequency impulse voltage kV 42/50/70
5 Rated current A 630
6 Rated open circuit load current (0.07Mpa//20℃  /h) A 630
7 Open circuit current under 0 pressure A 630
8 Rate peak value withstand current kA 50
9 Rated short-time closing current kA 50
10 Rated short-time withstand current kA/s 45677
11 Rated electric cable charge open circuit current A 25
12 Rated wire charge open circuit current A 16
13 Rated closed loop open circuit current A 630
14 Excitation current A 21
15 Rated current open circuit times 400 times
16 Rated working pressure MPa 0.07
17 Each operating voltage and resistance   150
18 Gas relative leakage rate year 0.01
19 SF6 gas moisture content Leave factory relative figure ppm 150
Switch working figure ppm 300
20 Machine stable operation times 6000
21 Rated operating voltage and assistant loop rated voltage V DC220;110
AC220;110
22 Weight M type kg 115
A type 135